凝縮溫度和表壓力
|
冰水出口溫度℃
|
冰水出入口溫差℃
|
冷卻能力
Kcal/Hr.
|
冷凍噸
RT
|
輸入電力
KW
|
冰水器水量
|
30℃
11.2kg/c㎡
(160 PSI)
|
12.5
|
5.84
|
309,130
|
102.2
|
62.5
|
(1)
設計參考值(約)
53.2M /HR
水壓
Max.3kg/c㎡
(2)
依據設計參考水量和本表資料之冷卻能力可計算出冰水出入口溫差。
|
10.0
|
5.30
|
283,940
|
93.9
|
61.5
|
7.5
|
4.72
|
259,160
|
85.7
|
60.6
|
5.0
|
4.28
|
234,380
|
77.5
|
60.4
|
35℃
12.9kg/c㎡
(184 PSI)
|
12.5
|
5.46
|
291,250
|
96.3
|
71.2
|
10.0
|
5.00
|
266,880
|
88.3
|
70.1
|
7.5
|
4.56
|
242,510
|
80.2
|
69.0
|
5.0
|
4.12
|
219,350
|
72.5
|
68.8
|
40℃
14.7kg/c㎡
(210 PSI)
|
12.5
|
5.20
|
277,030
|
91.6
|
76.4
|
10.0
|
4.73
|
253,880
|
84.0
|
75.6
|
7.5
|
4.28
|
231,540
|
76.6
|
74.8
|
5.0
|
3.87
|
210,010
|
69.4
|
74.7
|
45℃
16.7kg/c㎡
(239 PSI)
|
12.5
|
4.94
|
257,130
|
85.0
|
85.0
|
10.0
|
4.48
|
234,790
|
77.6
|
84.0
|
7.5
|
4.05
|
212,850
|
70.4
|
82.9
|
5.0
|
3.66
|
192,540
|
63.7
|
82.6
|
凝縮器冷卻水量設計參考值
|
冷卻水入口溫度 ℃
|
22
|
27
|
32
|
37
|
冷卻水量(約)
|
63.8M  /HR
|
冷卻水出口溫度 ℃
|
27
|
32
|
37
|
42
|
水壓
|
Max.4kg/c㎡
|
凝縮溫度 ℃
|
30
|
35
|
40
|
45
|
註1:本資料系敝公司冷凍特性性能試驗數據。
註2:可容許檢驗值±5%
|